PAE xxx-xxx1P-120 UQUI (Ultra-Quiet, Ultra Isolation) Transformer

10 KVA UQUI in NEMA 1 enclosure

The PAE UQUI Transformer series is designed specifically for powering audio and video production and editing suites.  It has a special core material and design which emits extremely low audible noise or chassis-borne vibrations.

Due to its double shields with very low inter-shield capacitance, it offers extremely high common-mode noise rejection, extremely low primary to secondary capacitance and has excellent voltage regulation over a wide range of loads.

The transformers can be ordered in NEMA type 1 or 3 cases depending on the particular application.  The PAE Ultra-Isolation transformer is electrician-friendly and features easy to access and terminate terminal lugs for all connections. A ground buss is supplied mounted inside the enclosure to make ground connections convenient.

Each transformer is a custom unit manufactured to our customer’s specifications to ensure optimum performance and value. We have supplied UQUI transformers ranging from 5 KVA to 50 KVA and others are available as requested. Send an email to: [email protected] to request further information or to schedule a consult.

SPECIFICATIONS:

  1. 208 or 240 single phase primary.
  2. Single 120 V Center-Tapped secondary.
  3. Double electrostatic shields with special low inter-shield coupling.
  4. 60 Hz standard, 50 Hz specials.
  5. 60°C rise max at full rated power.
  6. 2.5% voltage regulation from 10% to 80% power.
  7. NEMA ST-20 sound level or better.
  8. NEMA enclosures depending on customer requirements.
  9. Terminal Lug connections for quick, secure wiring.
  10. Wall or floor mounting depending on customer requirements and KVA rating.
  11. Dimensions depend on KVA rating and NEMA enclosure specified.

CONNECTIONS:

The PAE transformer is designed to take customer specified 208 V or 240 V AC, 60 Hz, and output 120 V.  It can be used in a normal transverse or balanced configuration.

In a normal transverse configuration the L1/L2 terminal is to be connected to both L1 & L2 in the Technical Power Breaker Panel.  The N terminal is connected to both Neutral and Ground per NEC 250.30 for Separately Derived Systems.

In a balanced configuration the transformer will supply 60 VAC from L1/L2 to CT, and 60 VAC from N to CT.  There will be 120 VAC between terminals L1/L2 and N. The CT terminal shall be grounded per NEC 647.6(A).  All circuit breakers in this configuration shall be GFCI 2-pole breakers of the appropriate amp rating.  All balanced power receptacles must be unique and incompatible with regular NEMA 5-15 receptacles per NEC 647.7(A)4.

Terminal Normal connection Balanced connection
H1 – H2 208 or 240 VAC per customer spec 208 or 240 VAC per customer spec
S1 Connect to incoming power ground Connect to incoming power ground
S2 Connect directly to technical ground point Connect directly to technical ground point
L1/L2 Connect to Technical Power Panel L1/L2 Connect to Technical Power Panel L1
CT No connection Connect to Technical Power Panel Ground
N Connect to Technical Power Panel Neutral/Gnd Connect to Technical Power Panel L2

PAE UQUI Typical terminal board diagram

Exclusive Warranty:

Pro Audio Group, LLC (“PAG”) dba Pro Audio Engineering, LLC., warrants to the original purchaser of the custom transformer (“Goods”) it will be free from defects in materials and workmanship for a period commencing on the date of manufacture of the Goods and expiring at the end of one calendar year. 

THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ANY OTHER WARRANTY EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

Warranty Exclusions – Limitation of Damages and Claims Procedure:

The above stated warranty does not cover: workmanship of installation; dissatisfaction or damage due to improper installation, vandalism, misuse, accident, excessive wear and tear, unauthorized repair, abnormal use, lack of maintenance, or other cause(s) not within PAG’s control.

PAG WILL NOT BE LIABLE, UNDER ANY CIRCUMSTANCES, FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR COSTS OR LOST PROFITS RESULTING FROM THE USE OF OR INABILITY TO USE THE GOODS OR FROM THE GOODS BEING INCORPORATED IN OR BECOMING A COMPONENT OR ANY OTHER PRODUCT.

Without limiting the generality of the foregoing, PAG will not be responsible for labor costs involved in the removal of any Goods or the installation of replacement Goods.  PAG’s liability and the Buyer’s exclusive remedy hereunder will be limited to repair or replacement of those Goods found in PAG’s reasonable judgment to be defective.  PAG reserves the right to accept or reject any claim in whole or in part. PAG will not accept the return of any Goods without its prior written approval.  Please consult PAG for instructions on the Return Authorization procedure.

© Copyright 2019, PAG, LLC